Floor Penetrations

Cabling and Pipework

  1. Home
  2. /
  3. Floor Penetrations
  4. /
  5. Firecrete EN HS Floor...
Floor Cutaway BLACK0738

Fire-stopping to cabling and pipework through floor openings using Sandersfire Firecrete EN HS.

Note: For load bearing seals please refer to structural data for thickness of Firecrete required.

FIRE PERFORMANCE AS FLOOR SEAL BS476 P.20, 1987
Depth of Firecrete (mm) Service Penetration Insulation (mins) On Services Integrity (mins)
100 EN HS Steel cable tray and cables 57 240
100 EN HS Steel pipe 25 - 108 dia 36 - 91 240
100 EN HS ASTM Cable trays, cables and steel pipes 59 - 180 240
100 EN HS Loaded Seal Clear Seal 220 240
FIRE PERFORMANCE AS FLOOR SEAL BS476 P.20, 1987 (HYDROCARBON CURVE)
Depth of Firecrete (mm) Service Penetration Insulation (mins) On Services Integrity (mins)
100 EN HS Steel cable tray and cables 22 - 200 245
100 EN HS Steel pipe 25 - 102 dia 36 - 91 245
EN HS: High Strength Firecrete Mortar